Product Description
FRAL have introduced these refrigerant models designed for commercial applications where very low humidity is required.
Previously only a desiccant dehumidifier would achieve this result. The FRAL FSDV8000 and FSDV6000 offer a more economical alternative without the inherent problems of the desiccants. Consider these quality commercial grade dehumidifiers to lower humidity down to 20%.
Note: 3 phase power supply required
Features:
- Works down to 20% R.H and 15˚C
- Star energy efficiency thanks to an exclusive dehumidifying process
- Automatic control of humidity
- Additional electric resistors for integrated functioning
- Monoblock unit with remote control possibility
- Structure in aluminium profiles with enclosing panels in strong galvanized painted steel sheet
- High efficiency filter
- High displacement motor fan
Price: $ P.O.A.
AIR VOLUME DATA – STATIC PRESSURE OF FAN MOTOR
Static Pressure |
100 |
200 |
300 |
400 |
500 |
600 |
700 |
Air volume cm/h FSDV6000 |
6400 |
6300 |
6200 |
6100 |
6000 |
5900 |
– |
Air volume cm/h FSDV8000 |
8600 |
8400 |
8300 |
8200 |
8200 |
8000 |
7600 |
CONDENSED WATER AT DIFFERENT AMBIENT TEMPERATURE AND HUMIDITY CONDITIONS – FSDV6000
25˚C 30% |
25˚C 40% |
25˚C 50% |
25˚C 60% |
30˚C 30% |
30˚C 40% |
30˚C 50% |
30˚C 60% |
35˚C 30% |
35˚C 40% |
35˚C 50% |
35˚C 60% |
160 l/d | 210 l/d | 260 l/d | 340 l/d | 225 l/d | 280 l/d | 350 l/d | 420 l/d | 250 l/d | 330 l/d | 440 l/d | 480 l/d |
CONDENSED WATER AT DIFFERENT AMBIENT TEMPERATURE AND HUMIDITY CONDITIONS – FSDV8000
25˚C 30% |
25˚C 40% |
25˚C 50% |
25˚C 60% |
30˚C 30% |
30˚C 40% |
30˚C 50% |
30˚C 60% |
35˚C 30% |
35˚C 40% |
35˚C 50% |
35˚C 60% |
210 l/d | 280 l/d | 340 l/d | 450 l/d | 300 l/d | 370 l/d | 460 l/d | 550 l/d | 330 l/d | 440 l/d | 580 l/d | 640 l/d |
TECHNICAL DATA
Power Consumption (at 30˚C, 40% rh) | FSDV6000
6000 w |
FSDV8000
8200 w |
Power Consumption (at 35˚C, 60% rh) | 8300 w | 10500 w |
Power Consumption with Electric Resistance & Fan Motor | 15 kW | 24 kW |
Power Consumption with Electric Resistance | 6 kW | 12 kW |
Absorbed Current (at 35˚C, 95% rh) in standard model 230/1/50 | 25 A | 36 A |
Noise level (at 3 meters) | 68 dB | 72 dB |
Refrigerant | R407c | R407c |
Defrost Control System | Electronic/Mechanical | Electronic/Mechanical |
Continuous Drainage Pipe (male) | 19mm | 19mm |
Temperature Range standard version | 15-38˚ C | 15-38˚ C |
Temperature Range hot gas defrost. version | 0.5-35˚ C | 0.5-35˚ C |
Relative Humidity Range | 20-70% | 20-70% |
Condensation Capacity (at 35˚C, 40% rh) | 300 l/24 hr | 420 l/24 hr |
Weight | 160 kg | 230 kg |
Dimensions (excluding filter) | 155cm x 76cm x 180cm | 180cm x 86cm x 200cm |
Working field 15-38˚C, 20-70% R.H.